Info & Specs
200 kW – 400 kW Output Configuration
AC Voltage | 480 VAC (3-phase) or user configurable |
Nominal Frequency | 50/60 Hz |
Nominal Charging Current | 250 A |
Nominal DC Bus Voltage | 780 VDC |
Capacitance | Configurable based on uptime requirements |
Uptime without supply | See Below |
VFD Size | Continuous: 385 A Overload: 450 A for 1 min |
Dimensions | L: 4169 mm (164 in) H: 2307 mm (90.8 in) D: 1000 mm (39.37 in) |
Environmental rating | NEMA 12, IP55 |
Seismic rating | Optional certified seismic frames available |
400 kW – 600 kW Output Configuration
AC Voltage | 480 VAC (3-phase) or user configurable |
Nominal Frequency | 50/60 Hz |
Nominal Charging Current | 500 A |
Nominal DC Bus Voltage | 780 VDC |
Capacitance | Configurable based on uptime requirements |
Uptime without supply | See Below |
VFD Size | Continuous: 520 A Overload: 690 A for 1 min 3(760 A for 1 min configurations available) |
Dimensions | L: 5952 mm (234 in) H: 2307 mm (90.8 in) D: 1000 mm (39.37 in) |
Environmental rating | NEMA 12, IP55 |
Seismic rating | Optional certified seismic frames available |
400 kW – 700 kW Output Configuration
AC Voltage | 480 VAC (3-phase) or user configurable |
Nominal Frequency | 50/60 Hz |
Nominal Charging Current | 500 A |
Nominal DC Bus Voltage | 780 VDC |
Capacitance | Configurable based on uptime requirements |
Uptime without supply | See Below |
VFD Size | Continuous: 520 A Overload: 690 A for 1 min 3(820 A for 1 min configurations available) |
Dimensions | L: 6731 mm (265 in) H: 2307 mm (90.8 in) D: 1000 mm (39.37 in) |
Environmental rating | NEMA 12, IP55 |
Seismic rating | Optional certified seismic frames available |
Performance Curve
In the case of a utility supply loss, the system will be able to maintain output for a period of time dependent upon the power being drawn and the total capacitance of the ION-Vaults®. For a given power draw and capacitance, consult the curves below for a theoretical approximation of this period of time.